Question: |
How do I select the correct
UnderAire™ Crawl Space Ventilator model
for my crawl space? |
Answer: |
Calculate the cubic area of the crawl
space by multiplying the
length × width × height. Divide this number by 15 to
determine the
minimum CFM necessary to fully ventilate the space in 15
minutes.
Example: 20’ wide × 40’ long × 3’ high crawl space =
2400 cubic ft. 2400
cubic ft. ÷ 15 = 160 CFM of ventilation. Choose two V1
or V1D
ventilators or one V2D ventilator. |
Question: |
Where should I mount the UnderAire™
Crawl Space Ventilator? |
Answer: |
Crawl Spaces are usually square,
rectangular or L shaped. The
UnderAire™ Crawl Space Ventilator should be installed to
provide
complete ventilation. As air is being vented out of the
crawl space, air will
be entering in from a foundation vent on the opposite
side of the crawl
space. The UnderAire™ exhausts stagnant air from the
crawl space while
fresh outdoor air enters foundation vents on the
opposite side of the crawl
space. |
Question: |
How do I know how many foundation
vents are needed? |
Answer: |
The UnderAire™ Crawl Space Ventilator
will do an air change every 15
minutes if properly sized. If you have an existing
structure you may
have foundation vents in place. It is recommended to
have a foundation
vent for each UnderAire™ installed on an opposite
foundation wall. If you
need to add a foundation vent or want to replace the
existing vent,
Tjernlund Products has the FV1 foundation vent
available. The
FV1 includes a cover that can be applied for the winter
months to
prevent air from entering the crawl space. |
Question: |
Can the UnderAire™ Crawl Space
Ventilator be installed on the outside of
the foundation wall? |
Answer: |
No. The UnderAire™ Crawl Space
Ventilator will need to be mounted on
the inside of the wall. This will protect the ventilator
controls from direct
contact with rain or snow. |
Question: |
If I do not have an outlet near the
UnderAire™ Crawl Space Ventilator
can I use an extension cord for a power source? |
Answer: |
The UnderAire™ Crawl Space Ventilator
requires 120 volt power supply.
Tjernlund Products recommends that the UnderAire™ plugs
directly into
the wall receptacle. It is also recommended the
receptacle be protected
with a GFI Ground Fault Interrupter. The UnderAire™
Crawl Space
Ventilator is suitable for damp locations. |
Question: |
Where should I position the
de-humidistat’s relativity humidity setting? |
Answer: |
A set point of 40% relative humidity
will maintain a comfortable
environment within the crawl space. Adjusting the set
point below 40%
relative humidity will maintain a drier crawl space by
operating the
UnderAire™ more frequently. Adjusting the set point
above 40% will
result in less frequent operation of the ventilator and
more moisture in the
crawl space. The Uniform Building Code requires all bare
ground crawl
spaces to be surfaced with poly covering of at least 6
mils thick. This
cover will keep the moisture out and promote a drier
crawl space. |
Question: |
My opening to mount the UnderAire™
Crawl Space Ventilator is smaller
than the mounting plate. Can the mounting plate be
trimmed to fit my
opening? |
Answer: |
In most cases the mounting plate can
be trimmed to fit the opening you are
working with. The V1D can be trimmed to fit a 6×10 inch
opening and the
V2D can be trimmed to fit a 6×15 inch opening. |
Question: |
Why doesn’t my UnderAire™ operate in
cold weather? |
Answer: |
All UnderAire Crawl Space Ventilators
have a built in low temperature
limit switch that is designed to stop fan operation once
the air temperature
drops below forty degrees Fahrenheit. When the outdoor
temperature
climbs above forty degrees Fahrenheit, the UnderAire™
will
automatically resume operation. |
Question: |
Where can I purchase the UnderAire™
Crawl Space Ventilator? |
Answer: |
Contractors are encouraged to contact
their local wholesalers for price and
availability. Otherwise Tjernlund Products has a link on
the “Home” page
of our site. In the upper right hand corner you can
select the Retail Store
link. Your purchase will be arranged with a direct
shipment to you using a
PayPal™ account. If you need assistance call Tjernlund
Products at
1-800-255-4208. |
SideShot®
Sidewall Vent Systems |
|
Question: |
When I use a SideShot® venting system
do I need to include a barometric draft control? |
Answer: |
Yes. The barometric draft control
(which is usually supplied with heating equipment) is
necessary for setting over fire draft adjustment on the
burner of an oil appliance. |
Question: |
Can I vent multiple heaters with one
SideShot®? |
Answer: |
Yes. You will need to add an MAC1E
interlock control to support the second appliance. It
will interface with the UC1 control allowing you to
interlock two individual appliances with one SideShot®.
Both appliances will need to share a common manifold or
vent connector prior to the inlet of the SideShot®. The
total “equivalent” length of allowable pipe for a
SideShot® is fifty feet. Each elbow must be counted as
ten feet. So the actual linear length of vent pipe is
usually less than fifty feet. There is also a BTU/hr
input limit that may not be exceeded. You can check the
sizing table on-line or you can contact Tjernlund
Products for assistance, 1-800-255-4208. |
Question: |
My foundation wall is 18 inches
thick. Do you make an extension for the SideShot®? |
Answer: |
The SideShot® wall thickness cannot
exceed 14” when using the SS1. When using the SS2 the
wall thickness cannot exceed 16”. For foundations that
exceed these maximum thicknesses use the HS Series side
wall vent systems. |
Question: |
My siding is vinyl. Should this be a
concern when side wall venting? |
Answer: |
One of the SideShot’s® designed
features is that it propells the flue gases straight
away in a horizontal direction. This prevents streaking
to the building’s exterior. For vinyl siding Tjernlund
recommends building a wood frame for mounting. The top
and sides use 1”x 2”and the bottom use 1”x 3”. The
inside frame opening will be 10 ½”wide by 8 ½” high.
This will provide a flush mounting surface wood frame to
secure the termination flange to. The contractor can
secure the “J-Channel” to the outside of the wood frame
keeping the SideShot® from coming into direct contact
with the vinyl siding. |
Question: |
The one side of my house that I can
vent through the side wall is directly under a deck. Is
that ok to terminate under the deck? |
Answer: |
Venting under a deck isn’t
recommended even though it is allowed. The flue gas odor
can be detected if you’re using your deck. If you have
an oil burner it may discolor the under side of the
deck, possibly turning it black. But, it is allowable if
there is a minimum of 12 inches between the top of the
SideShot® and the under side of the deck.
|
HS Series
Sidewall Power Venters |
|
Question: |
How do I size a side wall power
venting system? |
Answer: |
Tjernlund Products has a sizing tool
on line, visit “Tjernlund.com.” You will need the BTU/hr
input and fuel type of each appliance being vented by
the Power Venter. It is recommended to view the
Reference Guide for side wall venting. This literature
is available on line in the document library. Pipe
diameter, BTU/hr input and fuel type will determine your
model Power Venter. The sizing chart uses a 100 foot
total “equivalent” length maximum. To determine
equivalent feet, add the total length of straight vent
pipe plus 10 feet for each 90 degree elbow and 5 feet
for each 45 degree elbow. Once you select your Power
Venter using the Reference Guide you can also select a
termination hood. If you require assistance sizing
equipment contact Tjernlund Products at 1-800-255-4208. |
Question: |
When venting side wall what equipment
will I need? |
Answer: |
Once you have selected your power
venting system you can determine what additional
controls are needed. Tjernlund Products offers a few
vent packages for venting single appliances. These
packages are complete less the vent pipe. The GPAK is a
package for one gas furnace. The VP-2F and VP-3F are for
individual gas water heaters. The Side Shot® SS1 and SS2
are designed for fuel oil, natural gas and LP. The HS
series Power Venters include a UC1 control and fan
proving safety switch. The UC1 will allow a single
interlock directly between the appliance’s burner
circuit and the Power Venter. The UC1 control features a
voltage selection option. You simply set the voltage
selection pin to match the interlock voltage of the
burner circuit of the appliance: 115VAC or 24VAC. If you
have a millivolt appliance that is equipped with a
standing pilot and a thermocouple you will need a WHKE
interlock kit that will interface with the UC1 control.
If you have any questions contact Tjernlund Products,
Inc. at 1-800-255-4208. |
Question: |
Can I vent more than one appliance
with a single Power Venter? |
Answer: |
Yes. When venting multiple appliances
with a single Power Venter you must have a UC1 control.
As stated above GPAKs VP-2F, VP-3F and Side Shots® are
designed to vent one appliance only. Venting additional
appliances can be accomplished by adding either the
MAC1E or the MAC4E to the UC1. This will allow you to
support one additional appliance or four additional
appliances, respectively. When using any multiple
appliance control you will always be required to have
the UC1. Note if you are interlocking a millivolt
appliance (standing pilot, thermocouple) you also need
to add a WHKE Kit. All appliances need to share a common
manifold or vent connector on the inlet side of the fan.
The total BTH/hr cannot exceed the capacity of the Power
Venter. |
Question: |
Can I mount the Power Venter at the
appliance or do I need to keep it as close to the side
wall as possible? |
Answer: |
Tjernlund recommends that the Power
Venter is mounted at the side wall, connecting the
outlet collar of the fan to the termination hood. All
portions of vent pipe prior to the Power Venter inlet
are under negative pressure. Any vent pipe on the
discharge of the Power Venter is under positive
pressure. All vent pipe on the discharge of the fan must
be leak proof to ensure the flue gas doesn’t escape the
vent pipe joints. |
Question: |
Can I position my Power Venter to
terminate through the roof? |
Answer: |
Yes. The HS Series fans can be
mounted to discharge vertically. The motor shaft must be
mounted horizontally. All portions of the vent system
under positive pressure during operation (on the outlet
side of the Power Venter) shall be designed and
installed so as to prevent leakage of flue gases into
the building. |
Question: |
Do you offer replacement parts for
previous models? |
Answer: |
Yes. You can find a list of
replacement parts in the document library on our web
site. Visit
www.Tjernlund.com. |
Auto-Draft® Draft Inducer for Stoves |
|
Question: |
I have a wood stove with poor draft.
Will the AD-1 help improve this condition? |
Answer: |
These are conditions that cause poor
drafts: Your stove pipe or chimney may be undersized.
Your chimney may not be tall enough to ensure proper
draft. Your home may be located in a low lying area,
making your chimney susceptible to downdrafts. Your
chimney can also be affected by over hanging tree limbs
causing downdrafting. The AD-1, Auto Draft® Inducer
mounts into metal stove pipe. Pipe size can range from 5
to 8 inches. The AD-1 Auto-Draft® Inducer will improve
draft on a wood or coal stove. The AD-1 Auto Draft®
Inducer includes a speed control. The AD-1 can be
purchased on-line or through several distributors. If
you need assistance finding a distributor please contact
Tjernlund Products at1-800-255-4208. |
Question: |
When I put wood in the stove it
“puffs” smoke. Will the AD-1 eliminate this? |
Answer: |
When then the AD-1 is operating it
will eliminate any puff backs that occur when loading
your wood stove. |
Question: |
I have a masonry chimney. Can I use
the AD-1 Auto Draft® Inducer? |
Answer: |
The AD-1 must be mounted on metal
stove pipe. It may be used if you have stove pipe
connecting the wood stove to the masonry chimney. |
|
|
Question: |
I want to install an In-Line Draft
Inducer in Type B-vent pipe, is that ok? |
Answer: |
The In-Line Draft Inducer must be
installed in a section of single wall pipe, so that the
wheel has proper penetration into the pipe. Type-B vent
pipe may be used throughout the rest of the vent run. |
Question: |
Can I install an In-Line Draft
Inducer outdoors? |
Answer: |
No. The In-Line Draft Inducers need
to be installed indoors. A popular location is on the
horizontal pipe prior to the vertical rise of the
chimney. It is necessary to maintain three pipe
diameters on the discharge side of the Inducer prior to
the vertical rise of the chimney. Provide sufficient
support for the Inducer and all sections of vent pipe. |
Question: |
Can I vent more than one appliance
with an In-Line Draft Inducer? |
Answer: |
Venting multiple appliances can be
accomplished by using the UC1 and either the MAC1E or
the MAC4E. This will give you the ability to support a
total of two appliances when using the UC1 and the
MAC1E. If you’re venting more than two appliances, then
you will need the UC1 and the MAC4E, giving you the
ability to support up to five appliances. The UC1 and
MAC1E and the MAC4E interlock directly with 24VAC or
115VAC. Millivolt appliances, like, residential water
heaters, require a WHKE kit. This kit includes a gas
pressure switch that will actuate the Inducer. If you
need assistance sizing and selecting the right equipment
for your venting application feel free to contact
Tjernlund Products, Inc. direct at 1-800-255-4208 |
Question: |
Can I wire the Inducer to operate all
the time? |
Answer: |
Yes, but there must a safety
interlock in the event of Inducer malfunction. The
National Fuel Gas Code ANSI Z223. 1 paragraph 12.4.3.5
states: “Where a mechanical draft system is employed,
provision shall be made to prevent the flow of gas to
the main burners when the draft system is not performing
so as to satisfy the operating requirements of the
appliance for safe performance”. |
Question: |
As a homeowner can I purchase this
equipment directly from
Tjernlund Products, Inc.? |
Answer: |
No. Tjernlund Products sells its
venting equipment through Wholesale Distributors who in
turn, sell to Professional Contractors. The Contractor
will sell our equipment to you. |
VP Water Heater Vent Packages
Question: |
What does the water heater vent
system include? |
Answer: |
The water heater vent system is
designed to side wall vent, millivolt,
standing pilot gas water heaters. It includes everything
except the vent
connector and fittings. Included with the vent system is
the Power Venter, the termination hood and the controls
for actuation and safety. The water heater vent system
is CSA design certified. |
Question: |
My water heater uses PVC vent
connector. Can I use the water heater
vent system for this type of water heater? |
Answer: |
The water heater vent systems are not
compatible with condensing type
equipment. You must use all metal vent pipe. This type
of vent system is designed for atmospheric heaters. |
Question: |
Is there any restrictions to the size
of the water heater or how far I can vent
the appliance to the side wall? |
Answer: |
The VP-2F has an input rating of up
to 60,000 BTU/hr. The VP-3F is rated for BTU/hr input
loads from 60,000 to 120,000. Both models have a maximum
vent pipe allowable length of seventy-five feet total
“equivalent” length. 90 degree elbows are equivalent to
6 feet of straight vent pipe. |
Question: |
I have an older model VP-2. I am
replacing my water heater. It has an enclosed burner
chamber. Can I use the old VP-2 with my new water
heater? |
Answer: |
The Gas Pressure Switch (actuation)
has been redesigned for compatibility with enclosed
burner chambers. The part number is 950-2080.The new
style switch has a bleed orifice, instead of the
overflow tube. IF you use the existing switch you will
need to use ¼” copper AC tubing and route the overflow
to the outdoors. |
In-Line Draft Inducers
Question: |
I want to install an In-Line Draft
Inducer in Type B-vent pipe, is that ok? |
Answer: |
The In-Line Draft Inducer must be
installed in a section of single wall pipe, so that the
wheel has proper penetration into the pipe. Type-B vent
pipe may be used throughout the rest of the vent run. |
Question: |
Can I install an In-Line Draft
Inducer outdoors? |
Answer: |
No. The In-Line Draft Inducers need
to be installed indoors. A popular location is on the
horizontal pipe prior to the vertical rise of the
chimney. It is necessary to maintain three pipe
diameters on the discharge side of the Inducer prior to
the vertical rise of the chimney. Provide sufficient
support for the Inducer and all sections of vent pipe. |
Question: |
Can I vent more than one appliance
with an In-Line Draft Inducer? |
Answer: |
Venting multiple appliances can be
accomplished by using the UC1 and either the MAC1E or
the MAC4E. This will give you the ability to support a
total of two appliances when using the UC1 and the
MAC1E. If you’re venting more than two appliances, then
you will need the UC1 and the MAC4E, giving you the
ability to support up to five appliances. The UC1 and
MAC1E and the MAC4E interlock directly with 24VAC or
115VAC. Millivolt appliances, like, residential water
heaters, require a WHKE kit. This kit includes a gas
pressure switch that will actuate the Inducer. If you
need assistance sizing and selecting the right equipment
for your venting application feel free to contact
Tjernlund Products, Inc. direct at 1-800-255-4208 |
Question: |
Can I wire the Inducer to operate all
the time? |
Answer: |
Yes, but there must a safety
interlock in the event of Inducer malfunction. The
National Fuel Gas Code ANSI Z223. 1 paragraph 12.4.3.5
states: “Where a mechanical draft system is employed,
provision shall be made to prevent the flow of gas to
the main burners when the draft system is not performing
so as to satisfy the operating requirements of the
appliance for safe performance”. |
Question: |
As a homeowner can I purchase this
equipment directly from
Tjernlund Products, Inc.? |
Answer: |
No. Tjernlund Products sells its
venting equipment through Wholesale Distributors who in
turn, sell to Professional Contractors. The Contractor
will sell our equipment to you. |
Question: |
Can I operate multiple Duct Boosters®
with one PS1503 Duct Airstat™? |
Answer: |
Yes you can wire more than one Duct
Booster® to operate with the PS1503 Duct Airstat™. The
Duct Booster® motors will have to be wired in parallel
with the Duct Airstat™. |
Question: |
Do I need the service of a
professional Contractor? |
Answer: |
Tjernlund Products recommends that
you employ qualified, licensed service personnel.
Improper installation may result in fire, electrical
shock, carbon monoxide poisoning, personal injury and
/or property damage. |
Question: |
What is the best way to determine if
I need an In-Line Draft Inducer? |
Answer: |
These conditions may require an
Inducer: Undersized chimneys, or short chimneys
using vent systems will improve draft. Draft Inducers
are often installed when the horizontal pipe length
exceeds the code requirements. |
Dryer Duct Boosters®
Question: |
Will the Dryer Duct Booster® reduce
my drying time? |
Answer: |
Drying time will be shorter when
using the Dryer Duct Booster®. Dryer vent runs exceeding
twenty five-feet of duct lose velocity. When you add the
Dryer Duct Booster® you will maintain proper velocity,
reduce drying time and any lint build up in your dryer
duct. The shorter drying time will save energy. |
Question: |
What are the installation
requirements for the Dryer Duct Booster®? |
Answer: |
The LB1 must be installed 15’ feet
from the dryer and not any closer than 5’feet from the
termination. Do not install any elbows directly to the
inlet or discharge of the LB1. Maintain 12 inches of
straight duct on both sides of the fan. Use rigid duct.
Secure all joints with foil tape; do not use screws. If
you use flexible duct try to minimize its distance using
it only behind the dryer. Make sure there aren’t any
kinks. Use an exhaust hood that has a damper included,
preferably one that includes a 45 degree deflector
preventing against direct winds. |
Question: |
After I Install the Dryer Duct
Booster® and plug it in, how will it operate? |
Answer: |
The LB1 will automatically turn on
and off but not in unison with the dryer. Make sure the
dryer is empty and it is cool. Make sure the lint trap
is clean and the door of the dryer is closed. Plug in
the LB1. The LB1 will not turn on for about 30 seconds.
During these 30 seconds the LB1 control module is
establishing a baseline pressure. Once the LB1 starts,
it will record the pressure level it senses and then
turn off. The control module uses these set points to
turn the motor on/off. Wait two minutes to allow the
learn process to be completed. The next five dryer loads
are important to the booster operation. Clean the lint
trap after every dryer cycle. Let the dryer run a full
dry cycle and cool down cycle with each load. Do not
unplug the LB1 or you must repeat this procedure. For
assistance please call Tjernlund Products, at
1-800-255-4208. |
Question: |
My Dryer Duct Booster® will not turn
on with my dryer. I tried to reset the control. What
else can I do? |
Answer: |
Make sure no portions of the duct are
plugged or kinked. Check the discharge hood and make
sure there isn’t a blockage of lint holding the damper
open. After you unplug the LB1 make sure the dryer is
empty and cooled down. Clean the lint trap. Close the
door to the dryer and plug in the LB1. The LB1 will run
its program approximately thirty seconds after you plug
it in. Allow two minutes before starting the dryer. When
you turn the dryer on again, have a load of clothing in.
For assistance contact Tjernlund Products at
1-800-255-4208 |
Question: |
My Dyer Duct Booster® will not turn
off with my dryer. Should I unplug the LB1? |
Answer: |
Do not unplug the LB1, if the Dryer
Duct Booster® is running and the dryer has turned off.
Open the dryer door, close the door and turn the dryer
on for a minute. Turn the dryer off and open the door.
This will change the pressure in the duct, and the LB1
should turn off in two minutes or less. If you unplug
the LB1 you will need to re-program the control. |
|
|