SIDESHOT®
SERIES MODELS SS1 & SS2
|
SIDESHOT®
Series
Models:
SS2, SS1, SS1C
The SideShot® models SS1
and SS2 SideWall Vent Systems include the UC1
Universal Control for increased safety, performance and reliability. Designed for oil fired heating equipment or a deluxe gas vent system.
Patented vent termination propels flue gases at high velocities away from
the building exterior, a necessity when venting oil fired equipment. Both models can be installed with zero clearance to combustible materials
and have stainless steel construction in critical areas.
Factory wired safety and
operating controls allow simple interlock with any burner. The new model SS2
features a self-cleaning stainless steel, backward inclined impeller and sealed
ball bearing motor for virtually maintenance free installations. Ultra-fine
draft adjustment and slide-out access to all internal components. Easy multiple
appliance interlocks with our MAC Series
multiple appliance controls. |
|
|
|
SIDESHOT®
MODEL SS1
|
|
|
SIDESHOT® MODEL
SS1 APPLICATION TABLES
Verify that the total BTU/hr
input of the heating appliance(s) fall within the proper category listed
below. Please note the capacity differs between the SS1, SS1C and
SS2. To determine equivalent feet, add the total length of straight
vent pipe plus 10 feet for each 90 degree elbow and 5 feet for each 45
degree elbow. Vent runs over 15 linear feet should use an approved,
insulated vent connector to prevent problems related to condensation.
Multiple appliance interlocks require the use of our MAC-Series
Multiple Appliance Controls.
The SS1 & SS1C feature
a bottom or rear vent connection. The inlet collar accepts any brand
or type of 6" diameter vent pipe. |
SS1 CAPACITY
MODEL
|
NATURAL AND LP GAS
|
FLAME RETENTION OIL BURNER
|
CONVENTIONAL OIL
BURNER
|
MAX. EQUIVALENT FEET
|
SS1
|
50,000-160,00
BTU/hr.
|
50,000-220,000
BTU/hr.
1.55 gal/hr. max.
|
50,000-180,000
BTU/hr.
1.25 gal/hr. max.
|
50 feet
|
SS1C CAPACITY
(For larger residential and commercial applications)
MODEL
|
FLAME RETENTION
OIL BURNER
|
CONVENTIONAL
OIL BURNER
|
MAX. EQUIVALENT FEET
|
SS1C
|
50,000-315,000
BTU/hr.
2.25 gal/hr. max.
|
50,000-223,000
BTU/hr.
1.59 gal/hr. max.
|
50 feet
(15.2 meters)
|
SS1 DIMENSIONS
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H
|
I |
27 3/8"
|
16 1/2"
|
12 1/4"
|
8"
|
13 3/4"
|
15 1/8"
|
7 3/4"
|
14 3/4"
|
23 1/4 |
Note: The SS1 requires an 8"H x 8 3/8"W opening through the
wall
SIDESHOT®
MODEL SS2
|
|
|
SIDESHOT® MODEL
SS2 APPLICATION TABLES
Verify that the total BTU/hr
input of the heating appliance(s) fall within the proper category listed
below. Please note the capacity differs between the SS1, SS1C and
SS2. To determine equivalent feet, add the total length of straight
vent pipe plus 10 feet for each 90 degree elbow and 5 feet for each 45
degree elbow. Vent runs over 15 linear feet should use an approved,
insulated vent connector to prevent problems related to condensation.
Multiple appliance interlocks require the use of our MAC-Series
Multiple Appliance Controls. |
SS2 CAPACITY
MODEL
|
FLAME RETENTION
OIL BURNER
|
FAN ASSISTED
NATURAL & LP GAS
|
ATMOSPHERIC
NATURAL & LP GAS
|
MAX. EQUIV.
FEET
|
SS2
|
70,000-168,000*
BTU/hr.
|
40,000 - 150,000
BTU/hr.
|
40,000 - 125,000
BTU/hr.
|
50
|
*Maximum capacity based
on 13% CO2 and Max. 500o F. inlet temperatures.
Consult factory for details.
SS2 DIMENSIONS
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H
|
I
|
J |
32 1/2"
|
28 1/2"
|
5 1/2"
|
22 3/8"
|
7 3/4"
|
8"
|
12 1/2"
|
13 1/4"
|
10 1/2"
|
8 1/2" |
Note: The SS2 has a 4" vent connector. Install
full size vent pipe and reduce at SS2 connector.
The SS2 requires an 8 1/2"H x 10 1/2"W opening through the wall.
MODELS
HSJ, HS1, HS2
|
HS
Series
Models:
HSJ, HS1, HS2
The SideShot® Series is recommended for oil applications.
We recommend the use of our
HS-Series venters for oil burner inputs larger
than the SideShot® Vent System capacities. For Sidewall venting residential/light commercial natural gas, LP or oil
fired equipment including: Furnaces, boilers, water heaters and unit
heaters. All models feature the new UC1
Universal Control and a diaphragm Fan Proving Switch safety interlock
which will shut down heating equipment if a venting malfunction occurs. Built-in
adjustable damper also allows regulation for maximum
combustion efficiency. UC1 Universal Control
features include; adjustable pre and post-purge
settings, LED Status/diagnostic indicators, Fan Prover switch
monitoring. Interlocks with any 24-120 VAC burner control circuit
and also includes "dry" contact actuation option. Easily interlock
multiple appliances with our MAC-Series
multiple appliance controls.
|
|
MODEL
NUMBER
|
VENT
PIPE
DIA.
|
BTU/HR
INPUT
|
MAX. PIPE
LENGTH (FEET)
AT STACK TEMP.
GAS FIRED
300 F.
|
MAX. PIPE
LENGTH (FEET)
AT STACK TEMP.
GAS FIRED
400 F.
|
MAX. PIPE
LENGTH (FEET)
AT STACK TEMP.
OIL FIRED
500 F.
|
CFM AT 70 degrees F.
(Static Pressure)
0"
.50" .75" 1.0"
1.4"
|
HSJ**
|
4"
|
50,000
75,000
100,000
125,000
|
100'
100'
100'
35'
|
100'
100'
100'
23'
|
100'
100'
---
---
|
110
85 67 10
---
|
HS1**
|
4"
6"
|
150,000
200,000
250,000
300,000
150,000
200,000
250,000
300,000
|
100'
87'
40'
4'
100'
100'
100'
30'
|
60'
57'
12'
---
100'
100'
92'
---
|
35'
27'
---
---
100'
100'
---
---
|
158
115 95 12
---
|
HS2**
|
6"
8"
|
350,000
400,000
450,000
500,000
550,000
600,000
350,000
400,000
450,000
500,000
550,000
600,000
|
100'
100'
100'
100'
94'
15'
100'
100'
100'
100'
100'
67'
|
100'
100'
100'
72'
---
---
100'
100'
100'
100'
---
---
|
100'
100'
67'
---
---
---
100'
100'
100'
---
---
---
|
286
235 215 196
158
|
**Oil applications must use the
SideShot®
Vent Systems or HSJ, HS1, HS2 models which include UC1 Control with integral Pre and Post-Purge